33 Battery equalization
Battery equalization enable
Battery equalization disable
(default)
If “Flooded” or “User-Defined” is selected in program 05, this
program can be set up.
34 Battery equalization voltage
Default setting: 58.4V
Setting range is from 48.0V to
64.0V. Increment of each click is
0.1V.
35 Battery equalized time
60min (default)
Setting range is from 5min to
900min. Increment of each click
is 5min.
36 Battery equalized timeout
120min (default)
Setting range is from 5min to
900 min. Increment of each click
is 5 min.
37 Equalization interval
30days (default)
Setting range is from 0 to 90
days. Increment of each click is 1
day
39
Equalization activated
immediately
Disable (default)
Enable
If equalization function is enabled in program 33, this program can
be set up. If “Enable” is selected in this program, it’s to activate
battery equalization immediately and LCD main page will shows
“ ”. If “Disable” is selected, it will cancel equalization function
until next activated equalization time arrives based on program 37
setting. At this time, “ ” will not be shown in LCD main page.