PowerWalker Solar Inverter 5000 ZRO handleiding
Handleiding
Je bekijkt pagina 22 van 84

20
23 Bypass function:
Bypass Forbidden
If selected, inverter won’t work
in bypass/ECO modes.
Bypass disable
If selected and power ON button
is pressed on, inverter can work
in bypass/ECO mode only if
utility is available.
Bypass enable (default)
If selected and no matter power
ON button is pressed on or not,
inverter can work in bypass
mode if utility is available.
25 Record Fault code
Record enable
Record disable (default)
26
Bulk charging voltage
(C.V voltage)
default setting: 56.4V
If self-defined is selected in
program 5, this program can be
set up. Setting range is from
48.0V to 64.0V. Increment of
each click is 0.1V.
27 Floating charging voltage
Default setting: 54.0V
If self-defined is selected in
program 5, this program can be
set up. Setting range is from
48.0V to 64.0V. Increment of
each click is 0.1V.
28
AC output mode
*This setting is able to set
up only when the inverter is
in standby mode, Be sure
that on/off Switch is
in ”OFF” status.
Single
When the unit is operated alone,
please select “SIG” in program
28.
Parallel
When the units are used in
parallel for single phase
application, please select “PAL”
in program 28. Please refer to
5-1 for detailed information.