LCD Setting
General Setting
After pressing and holding “ ” button for 3 seconds, the unit will enter the setting mode. Press “ ” or “ ”
button to select setting programs. Press “ ” button to confirm you selection or “ ” button to exit.
S
etting Programs:
Program
Description
Selectable option
00 Exit setting mode
Escape
01
Output source priority:
To configure load power
source priority
Utility first (default)
Utility will provide power to the
loads as first priority.
Solar and battery energy will
provide power to the loads
only when utility power is not
available.
Solar first
S
olar energy provides power to
the loads as first priority.
If solar energy is not sufficient
to power all connected loads,
Utility energy will supply power
to the loads at the same time.
SBU priority
S
olar energy provides power to
the loads as first priority.
If solar energy is not sufficient
to power all connected loads,
battery energy will supply
power to the loads at the same
time.
Utility provides power to the
loads only when battery
voltage drops to either low-
level warning voltage or the
setting point in program 12.
02
Maximum charging current:
To configure total charging
current for solar and utility
chargers.
(Max. charging current =
utility charging current +
solar charging current)
60A (default)
Setting range is from 10A to
100A for 3.6kw model and
from 10A to 120A for 5.6kw
model. Increment of each click
is 10A.