PowerWalker MDC 6K42U handleiding
Handleiding
Je bekijkt pagina 14 van 138

6
Product overview
2.4 System specifications
The following table lists the system specifications.
System
Item
Description
System
Single cabinet size (W×D×H)
600 mm×1200 mm×2000 mm (42U)
Row cabinet size (W×D×H)
600×(3–7) mm×1400 mm×2000 mm (42U)
Number of cabinets
1–7 pcs
Power Usage Effectiveness (PUE)
Low as 1.34
Input power
–
Single cabinet: 220/230/240 Vac (L+N+PE) - 50/60 Hz
–
Row cabinets: 380/400/415 Vac (3Ph+N+PE) - 50/60 Hz
Installation site
Raised floor/Cement floor
Rack enclosure
and aisle
containment
system
Static load of the cabinet
1860 kg
Vibration level of the cabinet
Level 8 (YD5083-2005)
Color
RAL9005 (black)
Front/Rear door of single
cabinet/Row cabinet
Single glass door/Single metal door
Emergency Plan (Fire/High
temperature)
Pop-up front and rear doors (see Note 1)
Cooling system
Cooling capacity/set
3.5 kW (integrated cooling)/4.2 kW (Split cooling)/
8.1 kW (split cooling) (see Note 3)
Air flow/set
600 m
3
/h (3.5 kW
)
/800 m
3
/h (4.2 kW)/1600 m
3
/h (8.1 kW)
Air supply
Up
Installation method
Rack mounted
Power supply
subsystem
UPS power level
3 kVA/6 kVA/10 kVA/20 kVA
UPS installation method
Rack mounted
Power
distribution
system
Power distribution module form
factor
3–12U
Power distribution unit (PDU)
32A Basic type 0U PDU (standard IEC socket)
Monitored and managed PDU as an option
Monitoring
subsystem
Control monitoring server
0U monitoring module integrating user screen - single
cabinet/row cabinet
Remote monitoring
Web page (Google Chrome recommended)
Mobile APP (Android only)
Bekijk gratis de handleiding van PowerWalker MDC 6K42U, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | PowerWalker |
| Model | MDC 6K42U |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 22093 MB |