~ 24 ~
3.5 Determination of the Location and Position
3.5.1 Installation Angle Requirement
The battery can be floor-mounted and wall-mounted. The installation angles requirement is as follows:
• Do not install the battery at forward-tilted, back-tilted, side-tilted, horizontal, or upside-down positions.
3.5.2 Installation Position Requirements
Install the battery on a solid concrete structure or concrete wall or floor. If other types of walls and floors are
used, they must be made of fire-retardant materials and meet the load-bearing requirements of the equipment.
3.5.3 Installation Space Requirements
• During installation, ensure that there are no other devices or flammable or explosive materials around
the batteries. Reserve adequate space for heat dissipation and safety isolation.
• When the battery is mounted on a wall, do not place any objects under the battery.
Figure 12 Installation space
Note: Flammable or explosive materials or devices should be far from the battery packs.