● LS100-PIR: IP30 LoRaWAN Indoor Occupancy Sensor
The correct installation of LS100-PIR is shown below.
Please place it at a height of
2 to 2.2 meters from the ground.
Don’t place it near air conditioners,
refrigerators, and stoves.
Bonsai, glass, or curtain should not
obstruct the sensor from IR events.
Avoid direct sunlight.
2.2M
Sensor
Sensor
Sensor
Sensor
● Detection Range
Coverage area A-Distance:5meters;sensingangle:120°
Coverage area B-Distance:8meters;sensingangle:60°
Coverage area C-Distance:11meters;sensingangle:30°
● LS100-DW: IP30 LoRaWAN Door and Window Sensor
The distance between the two objects has to be less than 2 cm.
● LS200-TH: IP65 LoRaWAN Indoor Temperature and Humidity Sensor
Installation height recommendation: 1-2 m.
● LS200-PT: IP65 LoRaWAN Product Temperature Sensor
When LS200-TC is compared with the last reported values, the temperature
change is expected to exceed 0.1 °C (by default). It will report values at the
Min Time interval if it does not exceed 0.1 °C (by default). It will report values
at the Max. Time interval.