6). In the process of unit operation, once the compressor ceased, it should be 3 min delay for the next procedure.
5.2.4.3. IDU time delay: When compressor stops or unit switches off while in heating mode, IDU fan motor will work for
50 seconds.
5.2.4.4. ODU Fan motor control:
1). While unit:
a. To be switched off
b. Under protection.
c. To the set temperature
After compressor ceased, the fan motor stops working after 50s.
2). When switch on unit on heating mode, ODU fan motor will start up 3s ealier than compressor starts up.
3). In the process of defrosting, the fan motor will stop operation 39s delay after compressor stopped.
4). defrosting finish, the compressor stops operation, the fan motor will start working simultaneously.
5.2.4.5. 4-way valve control
1). On Cooling/Dry/Fan mode,4-way valve: OFF, when unit switched on heating mode,4-way valve: ON.
2). When heating mode switched off, or changed from heating to other modes, the 4-way valve will be OFF 2 min
delay after the compressor stops working.
3). Unit stops working caused by any kind of protection, the 4-way valve will be OFF 2 min delay.
4). In the process of defrosting, 4-way valve will be OFF 39s delay after compressor stopped.
5). When defrosting finish, the compressor stops operation, 4-way valve will be ON after 20s delay.
5.2.4.6. Defrost
Note: t1: compressor continuous works time.
t2: compressor accumulated working time.
t3:.The max value of (IPT – RT) when the compressor starts up after 8 minutes.
When AC unit working to:
a. T1 ≥ 120minutes
b. T2
≥
45minutes
c. t3 ≥ IPT – RT – 4℃
and it will start defrosting.
1) Defrosting start up: Compressor stops working, and re-starts to working after 44s delay;
2) Conditions for quitting defrosting
a. The defrosting for 10 min.
When AC meet any of condition a, defrosting finish.
3) Defrosting end off: Compressor stops working, and re-starts to working after 25s delay;
5.2.4.7. Cold air prevention:
This function intends to prevent cold air from being discharged when the heating operation starts up
1). IDU fan motor cold air prevention
1 .When RT<24℃(75.2℉):
a. If ITP>31℃(87.8℉) while compressor works for 5 min, fan motor will work according to preset fan speed.
b. If IPT≤31
℃(87.8
℉
)
, fan motor stops working while compressor operation within 2min, if IPT≥27
℃(89.6
℉
)
,
fan motor works in low speed 2 min, then change to preset speed.
2
When RT≥24℃(75.2℉):
a. Within 2 min after compressor start up working, once IPT
>
27
℃(89.6
℉
)
, fan motor will change to preset
speed.
b. After compressor starts working 2 min, fan motor change to preset speed directly.
2). Vane blade operation for cold air prevention.
a.
If the vane works on status of non-swing: While IPT increase to a special degree, the vane blade will change