2). When switch on unit on cooling mode, ODU fan motor will start up 3s ealier than compressor starts up.
5.2.2.4. When ODU failure or stops for protection, IDU works as preset.
5.2.2.5. Anti-frosting protection
Stopping the compressor to achieve anti-frosting protection.
1). After compressor starts up for 6 minutes, then if IPT < 0
for 3minutes
the compressor stops working.
2). After compressor starts up for 6 minutes, then if IPT < -2 for 3secondsthe compressor stops working.
3). Once compressor stops because of anti-frosting protection, compressor can restart only after IPT > 10℃.
5.2.3 Dry mode
5.2.3.1. Temperature control: 16~31
℃(60.8-87.8
℉).
Fan speed: low
Vane blade position: as customer preset
5.2.3.2. When ODU failure or stops for protection, IDU works as preset.
5.2.3.3. Compressor and process control
1). When RT-ST≥1, the compressor starts up working, AC operates as customer preset;
2). When
a. RT-ST<2℃,The compressor stops operation.;
b. -2℃≤RT-ST2The compressor starts up at first. The compressor will stop after starting up for 6minutes
and it will start up after stopping for 4minutes;
c. RT-ST> 2℃, The compressor starts operation.
4). The compressor will also stop working while unit:
a. switched off.
b. under protection.
c. changed to fan mode.
5). Under normal operation, the compressor can be stopped by program only working after 6 min once it starts up.
6). In the process of unit operation, once the compressor ceased, it should be 3 min delay for the next procedure.
5.2.3.4. Energy saving and sleep mode: Invalid.
5.2.3.5. Anti-frosting protection
Stopping the compressor to achieve anti-frosting protection.
1). RT-ST> 2℃: After compressor starts up for 6 minutes, then if IPT < 0 for 3minutesthe compressor stops
working.
2). RT-ST> 2
℃:
After compressor starts up for 6 minutes, then if IPT < -2
for 3seconds
the compressor stops
working.
3). -2℃≤RT-ST2: if compressor starts up for 3 minutes, and IPT < 0 for 3minutes, the compressor stops
working.
4). Once compressor stops because of anti-frosting protection, compressor can restart only after IPT > 10℃.
5.2.4 Heating mode
5.2.4.1. Temperature control: 16-31℃(60.8-87.8℉).
5.2.4.2. Compressor and process control.
1). When ST-CRT≥1
, the compressor starts up working, AC operates as customer preset;;
2). When
a. ST-CRT≤1℃,The compressor stops operation.;
b. -1
℃<
ST-CRT
1
℃,
The compressor remain state;
c. ST-CRT
1
℃,
The compressor starts operation.
3). The compressor frequency is fixed.
4). The compressor will also stop working while unit:
a. switched off.
b. under protection.
c. changed to fan mode.
5). Under normal operation, the compressor can be stopped by program only working after 6 min once it starts up.