3. If the unit has entered over-current stop-working protection 6 times consecutively, the protection can't be
recovered unless pressing the On/Off button. Once the compressor runs more than 6 min continuously, the counter
of the stop-working protection will be reset to zero, restarting the counting process.
Note: For different models, I
LC
and I
SC
have different programmed values.
5.2.10.4 IPM Overheating Protection
1. When IPM temperature T
IPM
≥189℉, the compressor will be frequency limited/reduced for IPM over-temperature
protection.
2. When T
IPM
≥203℉, the AC unit stops working for AC-system protection.
If T
IPM
<189℉ and after the compressor stops for 3 min, the unit can be started to operate.
3. If the unit has entered IPM over-temperature stop-working protection 6 times consecutively, the protection can't be
recovered unless pressing the On/Off button. The unit will show a failure code. Once the compressor runs more than
6 min continuously, the counter of the overload stop-working protection will be reset to zero, restarting the counting
process. The failure and times for protection will eliminate immediately once the unit is switched Off or changed to
Fan mode.
Note: If the defective failure can’t be recovered, the failure can’t be eliminated even if the operation mode changes.
5.2.11 Complementary
5.2.11.1 Energy Saving (Eco)
Function effective in Cooling and Heating modes only.
In Cooling mode, the set temperature range is from 79-88°F. In Heating mode, the set temperature range is from
61-77°F.
5.2.11.2 Turbo
Function effective in Cooling, Heating, Fan, and Auto modes. The fan speed operates on highest.
5.2.11.3 The Communication Control
If the ODU PCB can’t get signal feedback from the IDU for 2 min continuously, the AC unit stops operating and
displays the "E0" error code. The "E0" error code represents IDU/ODU communication failure. The unit can be
recovered to operate after the IDU and ODU communication recovers and the compressor stops for 3 min.
5.2.12 Calibration Test Mode
Turn On the indoor unit and within 3 min set the unit as:
1) Cooling mode.
2) Set temperature to
86°F
.
3) Mid-fan speed.
Press the Eco button 7 times consecutively within 8s and the unit will change to Calibration T
est mode. The buzzer
sounds 3 times.