Air Conditioner Service Manual
23
Note: The function setting:
Within 3 min of powering On the unit, set the unit to Cooling mode, temperature
to
86, and mid fan speed.
Press the Eco button 10 times consecutively within 8s and the Auto-Restart function activates.
5.2.10 Protection
5.2.10.1 Overload Protection
1. Overload Protection for Cooling or Dry Mode
1). If:
a. OPT≥144, the unit stops operating for overload protection.
b. OPT
131 and after the compressor stopped for 3 min, the unit can be started to operate.
2). When OPT≥131, the compressor will be
frequency limited/reduced for overload protection.
3). If the unit has entered overload stop-working protection 6 times consecutively, the protection can't be recovered
unless pressing the On/Off button. The unit will show a failure code. Once the compressor runs more than 6 min
continuously, the counter of the overload stop-working protection will be reset to zero, restarting the counting
process. The failure and times for protection will eliminate immediately once the unit is switched Off or changed to
Fan or Heating mode.
Note: If the defective failure can’t be recovered, the failure can’t be eliminated even if the operation mode changes.
2. Overload Protection for Heating Mode
1). If:
a. IPT≥144, the unit stops operating for overload protection.
b. IPT
131 and after the compressor stopped for 3 min, the unit can be started to operate.
2). When IPT≥131, the compressor will be frequency limited/reduced for overload protection.
3). If the unit has entered overload stop-working protection 6 times consecutively, the protection can't be recovered
unless pressing the On/Off button. The unit will show a failure code. Once the compressor runs more than 6 min
continuously, the counter of the doverload stop-working protection will be reset to zero, restarting the counting
process. The failure and times for protection will eliminate immediately once the unit is switched Off or changed to
Fan or Heating mode.
Note: If the defective failure can’t be recovered, the failure can’t be eliminated even if the operation mode changes.
5.2.10.2 Compressor Discharge Temperature Protection
1. If ODT≥239, the unit stops operating for over-temperature protection;
While ODT212 and after the compressor stopped for 3 min, the unit can be started to operate.
2. If ODT≥212, the compressor will be frequency limited/reduced for over-temperature protection.
3. If the unit has entered discharge over-temperature stop-working protection 6 times consecutively, the protection
can't be recovered unless pressing the On/Off button. The unit will show a failure code. Once the compressor runs
more than 6 min continuously, the counter of the discharge over-temperature stop-working protection will be reset to
zero, restarting the counting process. The failure and times for protection will eliminate immediately once the unit is
switched Off or changed to Fan mode.
Note: If the defective failure can’t be recovered, the failure can’t be eliminated even if operation mode changes.
5.2.10.3 Current Protection
1. If the A/C unit's working current is more than Limited current (I
LC
), the compressor will be frequency limited/
reduced for over-current protection.
2. If the A/C unit's working current is more than Stopped current (I
SC
), the AC unit stops working. Only when the
compressor stops for 3 min can the unit be recovered.