Air Conditioner Service Manual
21
a. t1≥t2, or
b. t3≤t1
t2
and also the temperature (related to OAT and OPT) tested 3 min continuously meets for defrosting.
1) Defrosting starts up: The compressor stops operating and restarts after a 50s delay.
2) Conditions for quitting defrosting:
a. After defrosting 60s, and OAT≥54 or
b. OAT-41, and OPT 46 for 80s continuously or
c. The defrosting for 10 min.
When AC meets any of condition a, b or c, defrosting finish.
COMPRESSOR
On
OUTDOOR FAN
4-WAY VALVE
Off
50S
50S
43S
48S
Defrosting max time
43s
7. Cold Air Prevention:
This function prevents cold air from
being discharged when the
heating operation starts
up.
1). IDU fan motor for cold air prevention:
When RT75:
a. If ITP
88
while the compressor works for 5 min, the fan motor will operate according to preset fan speed.
b. If IPT≤88, the fan motor stops operating while compressor operation within 2 min.
c. If IPT≥81, the fan motor operates in low speed for 2 min, then changes to preset speed.
When RT≥
75
:
a. Within 2 min after the compressor starts up and once IPT81, the fan motor changes to preset speed.
b. After the compressor starts working for 2 min, the fan motor changes to preset speed directly.
2). Vane blade operation for cold air prevention:
a.
If the vane works on the status of non-swing while IPT increases to a special degree, the vane blade will change
the position to:
--
Default angle or
-- Previous position or
-- Customer preset.
The above operation can only work one time. When the compressor stops operating, the unit will once again
inspect the function.
b.
If the vane works on the status of swing when the IDU quits from cold air prevention, the vane operates as preset.
8. 46 Heating
When this function is effective, it ensures the room temperature will not reach 46°F. Once the room temperature is
lower than 46°F, the unit operates in Heating mode.
5.2.5 Fan Mode
1. Temperature Setting: 61-88
Fan Speed and Vane Position: As preset. The function for remote controller 58E only.
3) Defrosting finishes: The compressor stops operating and restarts after a 50s delay.
t2: AC unit operation first time going to defrost circle.
t3: The compressor's accumulated working time. When OPT≤
37
, the
unit starts to count the time for t3.
When AC unit working to: