Air Conditioner Service Manual
20
a. ST-CRT≤27℉ and the compressor keeps 2 min continuously or
b. ST-CRT≤28℉ and the compressor works in the lowest frequency for 5 min continuously or
c. RT-CRT≤
30
℉
and the compressor works in the lowest frequency for 10 min continuously.
The compressor stops operation.
3). The compressor frequency control: Based on the relation of RT and ST and the changing speed of RT.
4). The compressor will also stop operating while the unit is:
a. Switched Off
b. Under protection
c. Changed to Fan mode
5). The compressor works for a minimum of 7 min before being stopped by its programming in normal operation (Active
cooling, heating, or an error code)
6). In the process of unit operation, once the compressor ceased, it should be a 3-min delay for the next procedure.
3. IDU Time Delay: When the compressor stops or unit switches Off while in Heating mode, the IDU fan motor will
operate for a few more seconds to prevent overheat.
4. ODU Fan Motor Control:
1). While unit:
a. Switched Off
b. Under protection
c. To the set temperature
32°F
27°F
28°F
30°F
ST-CRT
COMPRESSOR
OUTDOOR FAN
INDOOR FAN
2 min
10 min
5 min
≥ 7 min
160S
160S
≥3 min
4-WAY VALVE
5s
ON
OFF
33°F
6. Defrost
t1: The compressor continuous work time.
After the compressor ceased, the fan motor stops working according to the temperature of OPT and OAT. The max
delay for the motor should be less than 160s.
2). When switching the unit to Heating mode, the ODU fan motor will delay 5s after the compressor starts up.
3). In the defrosting process, the fan motor will stop operation for a 48s delay after the compressor stops.
4). When defrosting finishes, the compressor stops operation and the fan motor will start operating simultaneously.
5. 4-Way Valve Control:
1). In Cooling/Dry/Fan mode, the 4-way valve will be Off. When the unit switches to Heating mode, the 4-way valve will
be On.
2). When Heating mode switches Off or changes from heating to other modes, the 4-way valve will be Off for a 2-min
delay after the compressor stops working.
3). The unit stops working and is caused by any kind of protection, the 4-way valve will be Off for a 4-min delay.
4). In the defrosting process, 4-way valve will be Off for a 43s delay after the compressor stops.
5). When defrosting finishes, the compressor stops operation and the 4-way valve will be On after a 43s delay.