Phoenix Contact TP 6121-WXPS handleiding

32 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 16 van 32
TP 6…PS
14/30
PHOENIX CONTACT 4109_en_E
3.2.1 Power connection
Figure 3-5 Power connection
Connect a power source to the three-position removable connector. The connector (Order
No. 1777992) accepts wire sizes from 0.5 to 2.5 mm² (24 to 12 AWG). Torque the wire-re-
taining screws in the connector to 0.5 Nm (4.4 lb
f
-in.).
Connect the TP 6…PS to a 24 V DC power supply.
NOTE:
To ensure safe operation, use safety extra-low voltage (SELV) according to DIN
EN 61131 as a supply voltage.
This device is protection class I item of equipment.
3.2.2 Grounding
This is part of the power connector.
3.2.3 Ferrite core
NOTE:
A ferrite core is required for initial version of hardware, indicated on the product label
as VC00. Starting with VC01, the ferrite core is built into the internal power supply.
A ferrite core is included with the TP 6…PS units. It is required to reduce EMI interference
when the device is installed within the EEC.
Figure 3-6 Ferrite core
X1:PWR 24 VDC X2:USB
X3:USB