Configuration
107812_en_08 Phoenix Contact 31 / 82
Scalable analog inputs (TC MOBILE I/O X200-4G only)
The device can send up to four messages per analog input:
– Exceeding the upper tolerance
– Falling below the upper tolerance
– Exceeding the lower tolerance
– Falling below the lower tolerance
You can use the analog inputs as a voltage input (0 V ... 60 V) or as a current input
(0 mA ... 20 mA or 4 mA ... 20 mA). When a signal from 4 mA ... 20 mA is monitored, the
device can report wire break.
Figure 4-8 Scalable analog inputs
Relay
The device has four relays (N/O contacts). You can open or close the relays via a tele-
phone call or an SMS. A command can also switch several relays at the same time. For
security reasons, incoming emails are not supported.
If a relay was closed, it can automatically re-open itself after a freely selected waiting pe-
riod between one second and 999 hours. The device can send a confirmation SMS to the
recipient after a relay is opened or closed.
If the current fails or if the device restarts, the relay opens.