Installation
105608_en_01 PHOENIX CONTACT 53
Figure 6-5 Modbus connection
4. Finally, install the supply connections.
To do this, wire one of the supply inputs (+24 V) and (GND1) to the positive or negative
output of the supply device.
The remaining two free terminal blocks of the supply input on the communication module
can be used to implement the supply to other 24 V devices as a parallel connection. Note
the design of the power supply for all connected devices.
In order to avoid possible arc discharge during installation, do not connect the devices while
the power is connected.
Only switch on the power supply once the SOLARCHECK devices have been installed.
BA
390
390
220
A B GND2 A B GND2
MODBUS RTU (RS-485)
R
T
ControllerSCK-C-MODBUSSCK-C-MODBUS
1...31 MODBUS slaves