SOLARCHECK family
28
PHOENIX CONTACT 105608_en_02
4.2 Data acquisition and data transfer
The analog output of the voltage measuring module can be connected directly to the
0 V to 10 V input of the corresponding SCK-M-I-8S-20A SOLARCHECK current measuring
module. The measured values are then available via the SCK-C-MODBUS SOLARCHECK
communication module via RS-485 Modbus/RTU. As an option, the output can also be con-
nected to any analog 0 V to 10 V input of a controller, for example. Observe the installation
instructions in Section “Installing the SCK-M-U-1500V voltage measuring module” on
page 56 for integration and installation of the voltage measuring module. The voltage value
is mapped as a 2 V to 10 V signal. Due to the live zero point of the output, line break detec-
tion is integrated automatically (“live zero”).
4.2.1 Representation of voltage values at the analog output
The following calculation is used as the basis for mapping the system voltage values:
This results in the following value representation:
Figure 4-2 Value representation for voltage measurement
Y1 (left): decimal register value
Y2 (right): analog value (U_OUT)
X: system voltage
Table 4-4 System voltage calculation
Transfer function Resulting system voltage
U
2...10V OUT
=
()
2 V - 10 V
x U + 2 V
+-(HVin)
0 - 1500 V
U
+-(HVin)
=
()
2
x U - 375 V
2...10V OUT
375
6000
7000
8000
9000
10000
0 V
2 V
3 V
4 V
5 V
6 V
7 V
8 V
9 V
10 V
5000
4000
3000
2000
100 V
200 V
300 V
400 V
500 V
600 V
700 V
800 V
900 V
1000 V
1100 V
1200 V
1300 V
1400 V
1500 V
Y
1
Y
2
X

Bekijk gratis de handleiding van Phoenix Contact SCK-M-U-1500V, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkPhoenix Contact
ModelSCK-M-U-1500V
CategorieNiet gecategoriseerd
TaalNederlands
Grootte11551 MB