SOLARCHECK family
28
PHOENIX CONTACT 105608_en_02
4.2 Data acquisition and data transfer
The analog output of the voltage measuring module can be connected directly to the
0 V to 10 V input of the corresponding SCK-M-I-8S-20A SOLARCHECK current measuring
module. The measured values are then available via the SCK-C-MODBUS SOLARCHECK
communication module via RS-485 Modbus/RTU. As an option, the output can also be con-
nected to any analog 0 V to 10 V input of a controller, for example. Observe the installation
instructions in Section “Installing the SCK-M-U-1500V voltage measuring module” on
page 56 for integration and installation of the voltage measuring module. The voltage value
is mapped as a 2 V to 10 V signal. Due to the live zero point of the output, line break detec-
tion is integrated automatically (“live zero”).
4.2.1 Representation of voltage values at the analog output
The following calculation is used as the basis for mapping the system voltage values:
This results in the following value representation:
Figure 4-2 Value representation for voltage measurement
Y1 (left): decimal register value
Y2 (right): analog value (U_OUT)
X: system voltage
Table 4-4 System voltage calculation
Transfer function Resulting system voltage
U
2...10V OUT
=
()
2 V - 10 V
x U + 2 V
+-(HVin)
0 - 1500 V
U
+-(HVin)
=
()
2
x U - 375 V
2...10V OUT
375
6000
7000
8000
9000
10000
0 V
2 V
3 V
4 V
5 V
6 V
7 V
8 V
9 V
10 V
5000
4000
3000
2000
100 V
200 V
300 V
400 V
500 V
600 V
700 V
800 V
900 V
1000 V
1100 V
1200 V
1300 V
1400 V
1500 V
Y
1
Y
2
X