Phoenix Contact QUINT4-PS/3AC/24DC/20 handleiding
Handleiding
Je bekijkt pagina 24 van 36

QUINT POWER Software
24 / 36
PHOENIX CONTACT 107309_en_02
8.1.3 Output state
The signal output state is set to “High” or “Low”. The selected output state applies for as long
as the defined conditions, consisting of signal option and threshold value, are met.
Figure 8-2 Output state Out 1
In the configuration, output state Out 1 is specified with “High”. This applies for as long as
the output voltage is greater than 90 % of the set output voltage. If the output voltage falls
below the 90 % value, output Out 1 changes to “Low”.
8.1.4 Linking two signal options
You can link two signal options together for preventive function monitoring. To do this, select
the “Extended” tab and select the “ANDing” option in the corresponding drop-down menu.
8.2 Signal output Out 2
Output Out 2 is used as a digital or analog signal output for preventive function monitor-
ing. Different signal dependencies can be configured as required.
8.2.1 Digital
Signal options
Select a signal option from the listed parameters:
–Output voltage
– Output current
– Output power
– Operating hours
– Temperature OK
– Overvoltage Protection (OVP)
Additional signal option for 3AC/24DC/10A and 3AC/24DC/20A devices:
– Phase monitoring
Bekijk gratis de handleiding van Phoenix Contact QUINT4-PS/3AC/24DC/20, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Phoenix Contact |
Model | QUINT4-PS/3AC/24DC/20 |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 3051 MB |