Characteristics
107309_en_02 PHOENIX CONTACT 19 / 36
Example Your power supply has a nominal output voltage of 24 V and supplies a nominal output cur-
rent of 10 A. In order to compensate for the voltage drop over the cables, set the power sup-
ply output voltage to 26 V.
In the event of a short circuit, the power supply should shut down on the secondary side
when the FUSE MODE tripping current is exceeded. The absolute threshold value is then
calculated as follows:
Nominal output voltage:
Nominal output current:
Voltage set under “Output Voltage” category:
Relative FUSE MODE tripping current:
Absolute FUSE MODE tripping current:
U
N
= 24 V
I
N
= 10
A
U
Set
= 26 V
I
Fuse, rel
= 100 %
I
Fuse, abs
= I
Fuse, rel
U
N
I
N
U
Set
= 9.2 A