3.2 Supply via MINI MCR-SL-PTB... power terminals
For supplying power to MINI Analog modules, a particularly suitable method involves
MINI MCR-SL-PTB... power terminals. They have the familiar 6.2 mm housing and can be
seamlessly integrated into the MINI Analog range. Redundant supply is supported. The
decoupling of power supplies used for supply is ensured by the diodes integrated in the
module. Moreover, it is possible to extend mechanical redundancy by using two power
terminals. A 2.5 A fuse should be used to protect the power terminal(s). It is important to
make sure here that tripping is guaranteed in the event of a short circuit by the power
supply/supplies used. You can calculate the maximum number of modules, regardless of
whether you are using one or two MINI MCR-SL-PTB… modules, with the aid of the
product documents using the formula below.
Recommended fuse for power terminal:
Fuse according to IEC 60127-2/V
Nominal current: 2.5 A
Characteristic: slow-blow
(e.g., Wickmann 5 x 20 mm/No. 195 - glass fuse)
n
modules
I = n * I + n * I + n * I + ...
N 1 module1 2 module2 3 module3
I
max
I
N
I
N
2 A (4 A)
==