Phoenix Contact MINI MCR-2-I-I-ILP handleiding
Handleiding
Je bekijkt pagina 13 van 58

MINI Analog supply options
105810_en_02 Phoenix Contact 13 / 56
Then determine the maximum total current consumption of all eight modules.
The total current consumption of 158 mA is less than the maximum permissible current
for supply via a module. The fuse to be connected upstream of the supply signal condi-
tioner should have a nominal current of 500 mA. To ensure that the fuse definitely trips
in the event of a short circuit, the 24 V DC supply in this example is provided by a
QUINT4-PS/1AC/24DC/3.8/SC (item no. 2904599). The structure is shown in
Figure 3-2 on page 13. The wiring is as shown in Figure 3-1 on page 12.
Figure 3-2 Example for direct supply via a module
In addition to the low maximum number of modules, another disadvantage of this
method of supply is that fault monitoring is not possible. However, this function is
provided by the method of supply described in the next section.
8
7
6
5
QUINT4-PS/1AC/24DC/3.8/SC
UT 4-HESILED 24 (5X20)
MINI MCR-SL-PT100-UI-200-NC
MINI MCR-SL-PT100-UI-200-NC
MINI MCR-SL-PT100-UI-200-NC
MINI MCR-SL-PT100-UI-200-NC
MINI MCR-SL-UI-UI-NC
MINI MCR-SL-UI-UI-NC
MINI MCR-SL-UI-UI-NC
MINI MCR-SL-PT100-UI-200-NC
Bekijk gratis de handleiding van Phoenix Contact MINI MCR-2-I-I-ILP, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Phoenix Contact |
Model | MINI MCR-2-I-I-ILP |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 5905 MB |