Modbus/RTU communication (RS-485 interface)
UM EN MACX series_en_02 Phoenix Contact 29 / 43
30120 0x0077 1 Default value of parity and stop bit: 0 (No parity, 1 stop
bit)
/ Uint16
30201 0x00C8 2 L1-2 Voltage: for MACX-MR-3V-690-R-PT;
Voltage: for MACX-MR-V-600-R-PT;
Current : for MACX-MR-C-10-R-PT;
V/A Float32
30203 0c00CA 2 L2-3 Voltage
(Only for MACX-MR-3V-690-R-PT)
V Float32
30205 0x00CC 2 L3-1 Voltage
(Only for MACX-MR-3V-690-R-PT)
V Float32
30207 0x00CE 2 Degree of unbalance
(Only for MACX-MR-3V-690-R-PT)
% Float32
30209 0x00D0 1 Relay status:
0=Drop out;
1=Pick up.
/ Uint16
30210 0x00D1 1 Fault code 1 (latest):
0=No fault;
1=UV, undervoltage fault;
2=OV, overvoltage fault;
3=UC, undercurrent fault;
4=OC, overcurrent fault;
5=SEQ, phase sequence reversal fault;
6=FAIL, phase failure fault;
7=ASYM, asymmetry fault;
/ Uint16
30211 0x00D2 1 Whether L1-2/L1 has fault:
0=No;
1=Yes;
(Only for MACX-MR-3V-690-R-PT)
/ Uint16
30212 0x00D3 1 Whether L2-3/L2 has fault:
0=No;
1=Yes;
(Only for MACX-MR-3V-690-R-PT)
/ Uint16
30213 0x00D4 1 Whether L3-1/L3 has fault:
0=No;
1=Yes;
(Only for MACX-MR-3V-690-R-PT)
/ Uint16