Modbus/RTU communication (RS-485 interface)
UM EN MACX series_en_02 Phoenix Contact 27 / 43
6 Modbus/RTU communication (RS-485 interface)
The RS-485 interface serves localized networking with the Modbus/RTU communication
protocol. If the module is connected to a network and the distance exceeds 500 m, it is rec-
ommended to install one termination resistor (RT=120Ω) each on the side of the RS-485
converter and on the side of the last module on the line. For longer distances, a lower com-
munication speed (bps), low attenuation cable or signal repeater is required.
Table 6-1 Communication parameters
Figure 6-1 Modbus/RTU network
6.1 Device information/Measuring value
Table 6-2 Measuring value
Parameter Setting range Default setting
Address range 001…247 1
Baud rate 2400 bps, 4800 bps, 9600 bps, 19200 bps, 38400 bps, 57600 bps,
115200 bps
9600bps
Data bits Fixed 8 8
Parity & stop bit No parity/1 stop bit
Odd parity/1 stop bit
Even parity/1 stop bit
No parity/2 stop bits
No parity/1 stop bit
Decimal start address Hexadecimal start address Type Functions
30001 0x0000 Read 04