Phoenix Contact IB IL AO 4/U/0-10-ECO handleiding

190 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 16 van 190
IL SYS INST UM E
16 / 188 Phoenix Contact
6452_en_11
4 Important information about voltage areas
4.1 Voltage areas for Inline and Inline Block IO
Inline Block IO modules are available for the SELV area
Inline terminals are available for the SELV and low voltage areas. The terminals are di-
vided into three product groups according to their use in a specific voltage area and their
function.
Observe the safety notes in the following sections when working outside the protec-
tive extra-low voltage area.
Tabelle 4-1 Voltage ranges according to standards
Voltage range Permissible voltage Standard
AC DC
Low voltage 1000 V 1500 V
DIN EN 61140 (VDE 0140-1)
DIN VDE 0100-410
Extra-low voltage (ELV) 50 V 120 V
Protective extra-low voltage (PELV)
50 V 120 V
Safety extra-low voltage (SELV)
Protective extra-low voltage (PELV)
30 V 60 V
DIN EN 61131-2 (PLC standard)
DIN EN IEC 61010-2-201
Safety extra-low voltage (SELV)
Table 4-2 Voltage areas and corresponding terminal designations for Inline
Voltage area Voltage used for Inline Product group
Protective extra-low
voltage
24 V DC Extra-low voltage terminals;
Inline Block IO modules
Low voltage 120 V AC Low voltage terminals;
AC terminals
230 V AC
400 V AC Power-level terminals