Inline: Technical data and ordering data
6452_en_11 Phoenix Contact 159 / 188
Supply of terminals for digital signals (U
M
, U
S
) in the 24 V area
Nominal voltage 24 V DC
Permissible voltage range 19.2 V DC ... 30.0 V DC (incl. all tolerances, incl. ripple)
Load current at U
M
(main supply) See terminal-specific data sheet
Maximum 8 A
Terminal-specific 6 A (e.g., IB IL 24 PWR IN/2-F-PAC)
4 A (e.g., IB IL 24 PWR IN/2-F-D-PAC)
Load current at U
S
(segment supply) See terminal-specific data sheet
Maximum 8 A
Terminal-specific 6 A (e.g., IB IL 24 SEG/F-PAC)
4 A (e.g., IB IL 24 SEG/F-D-PAC)
2.5 A (e.g., IB IL 24 SEG-ELF-PAC)
Observe the specifications in the terminal-specific data sheet for the terminal used for power supply (U
M
/U
S
).
These terminals can limit the maximum permissible load current.
Connection to corresponding terminals for supply Inline connectors
Connection within the Inline station Inline potential jumpers
Supply of terminals for digital signals (L) in the 120 V AC and 230 V AC areas
Nominal voltage 120 V AC
230 V AC
Permissible voltage range 12 V AC ... 253 V AC (incl. all tolerances, incl. ripple)
Load current 8 A, maximum
Connection Inline potential jumpers