Connecting cables
6452_en_11 Phoenix Contact 133 / 188
12.2 Connecting the power supplies
Inline To operate an Inline station you must provide the supply voltage for the bus coupler, the
logic of the terminals, and the sensors and actuators.
Connect the power supplies using unshielded cables as described in Section “Connecting
unshielded cables” on page 128.
For the connector pin assignment of the supply voltage connections, please refer to
the terminal-specific data sheets for bus couplers, power terminals, and segment
terminals.
Inline Block IO When using Inline Block IO modules, the supply voltage for the module and the sensors
and actuators must be provided. Depending on the module, connection can be via Inline
connector or COMBICON connector.
The power supplies are connected using unshielded cables. For connection via Inline
connector, see Section “Connecting unshielded cables” on page 128.
For the connector pin assignments for connecting supply voltages, please refer to
the relevant module-specific data sheet.
12.2.1 Inline: Supply options
Bus coupler supply
For detailed information, please refer to the documentation for your bus coupler.
Power terminal supply
Depending on the type of power terminal, the following supply voltages can be supplied
or provided:
– U
M
and U
S
(I/O supply voltage)
– U
24V
(generation of U
L
and U
ANA
), U
M
, and U
S
(communications power and I/O supply
voltage)
Please also refer to the information provided in Section “Power, segment, and ac-
cessory terminals” on page 30.
Providing the segment voltage at segment terminals
At segment terminals, the segment voltage U
S
is provided from the main circuit U
M
.
Please also refer to the information provided in Section “Power, segment, and ac-
cessory terminals” on page 30.
Notes on supply voltages
The bus coupler supplies the module electronics of the connected terminals with com-
munications power (U
L
), which is generated, for example, from the bus coupler supply
voltage (U
BK
). If the supply voltage U
BK
is disconnected, the bus stops.
The supply voltage to the sensors and actuators (U
M
/U
S
) should be installed and
protected independently of the bus coupler supply (U
BK
). In this way the bus continues
to run even if some I/O devices are switched off.