Errors: Messages and removal
8220_en_06 PHOENIX CONTACT 53
2
IN_DATA_VALID (slot 2),
PROFINET system 1
TRUE
Slot 2:
Application relationship (AR) fully established between
PROFINET IO controller 2 and the safe PROFINET gateway
(PROFINET IO device in PROFINET system 2) and process data is
being exchanged (output data from PROFINET IO controller 2 to
safe PROFINET gateway (PROFINET IO device in PROFINET sys-
tem 2) is valid).
FALSE
Slot 2:
Application relationship (AR) not established between
PROFINET IO controller 2 and the safe PROFINET gateway
(PROFINET IO device in PROFINET system 2).
Output data from PROFINET IO controller 2 to safe PROFINET
gateway (PROFINET IO device in PROFINET system 2) is
invalid.
IN_DATA_VALID (slot 2),
PROFINET system 2
TRUE
Slot 2:
Application relationship (AR) fully established between
PROFINET IO controller 1 and the safe PROFINET gateway
(PROFINET IO device in PROFINET system 1) and process data is
being exchanged (output data from PROFINET IO controller 1 to
safe PROFINET gateway (PROFINET IO device in PROFINET sys-
tem 1) is valid).
FALSE
Slot 2:
Application relationship (AR) not established between
PROFINET IO controller 1 and the safe PROFINET gateway
(PROFINET IO device in PROFINET system 1).
Output data from PROFINET IO controller 1 to safe PROFINET
gateway (PROFINET IO device in PROFINET system 1) is
invalid.
Table 5-1 Bits of the diagnostic/status word at slot 1
Bit Name State Meaning