Phoenix Contact FL PN/PN SDIO-2TX/2TX handleiding
Handleiding
Je bekijkt pagina 11 van 94

For your safety
8220_en_06 PHOENIX CONTACT 11
1.2 Electrical safety
Direct/indirect contact Protection against direct and indirect contact according to VDE 0100 Part 410 must be
ensured for all components connected to the system. In the event of an error, parasitic
voltages must not occur (single-fault tolerance). This also applies to devices and
components with hazardous contact voltages that are permanently connected to the
network and/or diagnostic interfaces of the devices used.
This requirement can be met by:
– Using power supply units with safe isolation (PELV).
– Decoupling circuits, which are not PELV systems, using optocouplers, relays, and other
components, which meet the requirements of safe isolation.
Power supply unit for
24 V supply
Insulation rating When selecting the operating equipment, please take into consideration the contamination
and surge voltages, which may occur during operation.
The FL PN/PN SDIO-2TX/2TX safe PROFINET gateway is designed for surge voltage
category II (according to DIN EN 60664-1). If you expect surge voltages in the system,
which exceed the values defined in surge voltage category II, take into consideration
additional measures for voltage limitation.
WARNING: Hazardous body currents and the loss of functional safety
Disregarding instructions for electrical safety may result in hazardous body currents and
the loss of functional safety.
In order to ensure electrical safety, please observe the following points.
WARNING: Loss of electrical safety and the safety function when using unsuitable
power supplies
The FL PN/PN SDIO-2TX/2TX safe PROFINET gateway is designed exclusively for
protective extra-low voltage (PELV) operation according to EN 60204-1. Only PELV
according to the defined standard may be used for supply purposes.
The following applies to the network and the I/O devices used in it:
Only use power supply units that meet EN 61204 with safe isolation and PELV according
to EN 50178/VDE 0160 (PELV). This prevents short circuits between primary and
secondary sides.
Make sure that the output voltage of the power supply does not exceed 32 V even in the
event of an error.