ECM – multifunctional current measuring transducers
28 / 78 Phoenix Contact
111433_en_00
Zero point suppression
Activate zero point suppression to specify the response threshold of 0.5% for the relevant
measurement range end value. Up to a threshold of <0.5%, the measurement is output
as zero.
4.1.5 Setting average values
4.1.5.1 Method: Fixed interval
Figure 4-6 Average value over fixed interval
Interval
Specify the duration of the measurement interval in seconds from which the current and
frequency average values (AVG) are calculated.
Digital input sync.
This option is only available for devices with analog output.
Activate this option to trigger the start time of the fixed interval via an external signal and
thus synchronize both processes. The voltage level must be <30 V for this.
The average value is calculated over a fixed time interval (e.g., 900 seconds)
and recalculated after the fixed time period has elapsed.