ECM – multifunctional current measuring transducers
22 / 78 Phoenix Contact
111433_en_00
Table 3-3 Connection assignment for ECM-UC-10(0)A-MTCP
Connection termi-
nal block
Signal Description
2.1 +24V Operating voltage
2.2 +24V Operating voltage
2.3 GND1 Reference ground for operating voltage
2.4 GND1 Reference ground for operating voltage
3.1 ... 3.4 Not used
X1 RJ45 jack Ethernet interface (Modbus/TCP, web server)
Terminal blocks 6.1 ... 6.4 only apply to ECM-UC-10A-MTCP
6.1 0.1 A/1 A Input for current measurement range
6.2 5 A Input for current measurement range
6.3 10 A Input for current measurement range
6.4 GND Reference ground for inputs for current
measurement ranges
• The devices support 10 Mbit/100 Mbit full/half duplex
• Use at least Cat5 cables (EIA/TIA-568) for installation