Wiring
109908_en_02 Phoenix Contact 31 / 150
5.2.1 Wiring precautions
– Use a bladed screwdriver (2.5 mm wide × 0.4 mm thick) to press on the lever to
remove the wiring.
– When wiring litz wires, ensure that they are perfectly arranged to go through the
wiring holes.
– <5 m unshielded cable
– >5 m ... <30 m unshielded twisted cable possible
– >30 m shielded cable
– 50 m maximum permissible cable length
Table 5-1 Terminal description
Terminals Description
24V OUT Digital control signal supply
+24 V DC ±10% 100 mA
SPEED1/R SPEED1/R input
SPEED2/L SPEED2/L input
RESET RESET input
GND Ground reference point for digital control signals
DO Digital output
Speed1/R / Speed2/L active: DO output 24 V
Speed1/R / Speed2/L not active, but ramp: DO output 24 V
Speed1/R / Speed2/L not active and no ramp: DO output 0 V
11
12
14
Feedback relay
11-12: NO (N/O contact)
11-14: NC (N/C contact)
10V OUT The terminal can be used as a power supply for an analog signal or for
supplying the contact side of a temperature monitoring relay.
PTC/AI The terminal can either be used to connect a monitoring relay or as an
input for an analog input signal.
AGND Reference potential for the analog input
24V OUT 24 V output for STO+ signal
STO+ Delivery state: STO+ bridged to 24V OUT and STO- bridged to GND
For further information, see Section “STO – Safe Torque Off” on page 105.
STO-
GND Ground output for STO- signal