Phoenix Contact CHARX PS/3AC/920DC/87.5KW handleiding

96 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 59 van 96
Startup
109484_en_01 PHOENIX CONTACT 59 / 94
6 Startup
Perform a startup in the following cases:
During first startup of the system
After modifications or repairs
Required tools
To start up the system, you require the following:
Voltage tester, e.g., DUSPOL
Rotating field measuring device
Several screwdrivers
6.1 Safety notes for startup
DANGER: Danger to life from missing protective conductor
A flawless grounding connection has to be established before connection to the
mains.
DANGER: Danger to life from electric shock
Severe or fatal injuries when touching cables and terminal blocks in the device.
DANGER: Potentially lethal voltage
When working on the system, observe the correct scope and condition of your per-
sonal protective equipment.
Please note:
Do not mix up the polarity of mains inputs L and N.
Before initial startup, check that grounding and mains installation are correct.
Before startup, check the system for contamination.
Avoid impurities in the supply air. If the large fans in the front of the DC power module
suck in impurities, these immediately get into the DC power module and might cause
short circuits. As a result, the DC power module fails completely.

Bekijk gratis de handleiding van Phoenix Contact CHARX PS/3AC/920DC/87.5KW, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkPhoenix Contact
ModelCHARX PS/3AC/920DC/87.5KW
CategorieNiet gecategoriseerd
TaalNederlands
Grootte6956 MB