Installation
109484_en_01 PHOENIX CONTACT 53 / 94
5.8.4 Recommended conductor cross-sections, mains input
WARNING: Risk of fire from wrong cross section
The following table only provides an overview of the current carrying capacity for in-
stallation type C/30°C. The actual cross sections and fuses have to be selected with
regard to ambient temperature, number of cables and cable lengths, and according to
local regulations.
WARNING: Risk of fire from wrong conductor cross-section
Specify the minimum cross section in accordance with EN 62040-1 and
EN 60950-1, Table 3b.
Select the conductor cross-section depending on the following factors:
– The fuse externally connected upstream of the cabinets
– The installation method in accordance with IEC 60364-5-52 and VDE 0100-520,
Table 1
Observe the local and country-specific requirements.
NOTE: Incorrect dimensioning of the mains supply
If 4-pos. disconnect elements are used to protect the system, observe the following.
In situations with non-linear consumers and high harmonic content, the neutral con-
ductor current can be larger than the phase current.
Please note:
– For operating the system, using a neutral conductor at the input is mandatory.
– Observe all local or national regulations for electrical installations. These may be coun-
try-specific.
– The conductor cross-section should be dimensioned in such a way that, with the cable
length used, the ohmic voltage drop is limited to <1%.
– All incoming and outgoing cables have to withstand at least 75°C.
– Select the cross section of the AC mains cable so that line losses are as low as possible
(maximum possible cross section at minimum cable length).
– Overcurrent protection has to be provided at the AC input.
– Observe the following tables for correct dimensioning of fuses and cable cross-sec-
tions for the mains connection and consumer connection.
– Prior to connection, make sure that the mains input voltage and the mains frequency
correspond to the rating plate.