Phoenix Contact AXL F BP SE4 handleiding

40 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 8 van 40
UM EN AXL F SYS DIAG
8 / 38 Phoenix Contact
8663_en_08
2.1.2.2 D indicator on Axioline F backplanes
Figure 2-3 D LEDs on an Axioline F backplane
One D LED (red, yellow, green) is assigned to each slot for a Smart Element.
Each D LED signals the state of the local bus of the assigned slot.
The firmware of the bus head determines whether a bus head (bus coupler or controller)
supports operation with passive Smart Elements. The blink codes of the bus head like-
wise depend on the firmware.
The following controllers and bus couplers support the Smart Elements AXL SE SC and
AXL SE PD ... from the specified firmware version:
Controllers and bus couplers not listed in the table do not support the AXL SE SC and
AXL SE PD ....
Table 2-2 Support of AXL SE SC and AXL SE PD ...
Order No. Type Firmware version
Controllers
2700988 AXC 1050 ≥ 5.0
2700989 AXC 3050 ≥ 6.3
1151412 AXC F 1152 ≥ 2020.0
2404267 AXC F 2152 ≥ 2020.0
1069208 AXC F 3152 ≥ 2020.3
Bus couplers
2688459 AXL F BK ETH ≥ 1.30
2701949 AXL F BK ETH XC ≥ 1.30
2688394 AXL F BK EIP ≥ 1.30
2702782 AXL F BK EIP EF ≥ 1.30
2403869 AXL F BK PN TPS ≥ 1.30
1068857 AXL F BK PN TPS XC ≥ 1.30
2688899 AXL F BK EC ≥ 1.30
2701686 AXL F BK S3 ≥ 1.35
2688530 AXL F BK PB ≥ 2.20
2702463 AXL F BK PB XC ≥ 2.20