Phoenix Contact AXL F BP SE4 handleiding
Handleiding
Je bekijkt pagina 5 van 40

Diagnostics in the Axioline F system
8663_en_08 Phoenix Contact 5 / 38
2 Diagnostics in the Axioline F system
Axioline Smart Elements are integrated into an Axioline F station using
Axioline F backplanes. Although the Axioline Smart Elements are not explicitly
mentioned in each instance, the explanations in this document also apply to the
Axioline Smart Elements in connection with the Axioline F backplanes.
Terms used in the document:
The Axioline F modules indicate the errors that occur in various ways:
– Via the local diagnostic indicators
– Via diagnostic object 0018
hex
(DiagState)
– Via the diagnostic registers of the AXC ... controllers
– Via the diagnostic registers of the AXL F BK ... bus couplers
2.1 Local diagnostic and status indicators
All Axioline F modules are provided with diagnostic and status indicators for quick local
error diagnostics. They enable the clear localization of system errors (bus errors) or I/O
errors.
Diagnostics The diagnostic indicators (red, yellow or green) provide information about the state of the
module and, in the event of an error, provide information about the type and location of
the error. The module is working correctly when all of its green LEDs are on.
Status The status indicators (yellow) indicate the status of the associated input or output and of
the connected I/O device.
Extended diagnostics Some modules have extended diagnostics. For example, this enables a short circuit or
overload of the sensor supply to be detected and reported. If a short circuit occurs at an
output, some output modules can diagnose each channel individually. Information about
the supply voltage is also reported. The module sends information about I/O errors to the
controller with precise details of the error type. In addition, the status indicators signal
the error.
Only the D (diagnostics for local bus communication) and E (error) LEDs are de-
scribed below.
For an overview of all the main diagnostic and status indicators in the Axioline F sys-
tem and their meaning, please refer to the UM EN AXL F SYS INST user manual.
For information regarding the diagnostic and status indicators on a particular mod-
ule and their meaning, please refer to the module-specific documentation.
Local bus Axioline F local bus
Head of an Axioline F station E.g., Axioline F bus coupler, Axioline F controller
Local bus master Part of the head of the Axioline station that is responsi-
ble for controlling the Axioline F local bus
Axioline F module Any module of an Axioline F station,
i.e., head of the Axioline F station or I/O module
Bekijk gratis de handleiding van Phoenix Contact AXL F BP SE4, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Phoenix Contact |
Model | AXL F BP SE4 |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 3843 MB |