Phoenix Contact AXL F BP SE4 handleiding

40 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 27 van 40
Error codes
8663_en_08 Phoenix Contact 27 / 38
3.3 Error codes when invoking the PDI services
In Table 3-3, the additional code is only specified if it contains a special value. The
standard values for the additional code are listed in Table 3-4.
The code consists of the error code and error class.
Example:
Code = 0501
hex
: Error class = 05
hex
, Error code = 01
hex
Table 3-3 Error codes when invoking the PDI services
Code
(hex)
Additional
code
Meaning Remedy
02xx Error in the communication relationship Check the invocation.
0200 Miscellaneous error
0201 Unable to access the object.
Possible causes:
Module not present
Incorrect module number
05xx Invalid service Check the invocation.
0500 Miscellaneous error
0501 The current object state is preventing the service from
being executed.
0502 Problem with the PDU size
Permissible length exceeded. Object cannot be read in
full.
0503 The service cannot be executed at present.
0504 The service contains inconsistent parameters.
0505 A parameter has an impermissible value.

Bekijk gratis de handleiding van Phoenix Contact AXL F BP SE4, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkPhoenix Contact
ModelAXL F BP SE4
CategorieNiet gecategoriseerd
TaalNederlands
Grootte3843 MB