1002985, B21110_EN_rev4 8 10/06/2022
Functional Safety
Mode of operation Continuous, High Demand
Failure Rate
ʎ
SD
488 ʎ
SU
235 ʎ
DD
267 ʎ
DU
9 S
FF
99.1%
Supported Safety Integrity Levels SIL3
Demand Response Time 8.5 Seconds
Device Type Type A
Systematic Capability SC 3
Error Handling Response Time 12.1 Seconds
Reference Report PAN 19/08-093 R001
Operating Modes SIL mode only
Hardware Fault Tolerance (HFT) 0
Standards and Certifications
UL 1436 Standard for outlet circuit testers and similar indicating devices
CAN/CSA-C22.2 No. 160 Voltage and polarity testers
IEC / UL / CSA C22.2 NO. 61010-1
IEC / UL / CSA C22.2 NO. 61010-2-030
Safety requirements for electrical equipment for measurement, control, and laboratory use
UL 508 & CSA-C22.2 No. 14 Industrial control equipment
IEC 61508-1, -2, and -3 {SIL 3 Rating} Functional safety of electrical/electronic/programmable safety-related security systems
FCC - CFR 47 Part 15 Subpart B Radio frequency devices
CAN ICES-001 Industrial, scientific and medical (ISM) radio frequency generators
EN 55011, CISPR 11
AS/NZS CISPR 11
Radio frequency disturbance characteristics
IEC / EN 61326-1, -3-1 EMC and immunity requirements
IEC / EN 61000-3-2, -3-3, -6-2 Electromagnetic compatibility (EMC)
CE
UKCA
Conformity Marking for European Economic Area
Conformity Marking for United Kingdom
RoHS Restriction of hazardous substances
NOTE: By design and installation guidelines the VeriSafe 2.0 AVT is not impacted by the occurrence of phenomena from IEC 61000-4-16