10/06/2022 13 1002985, B21110_EN_rev4
Installation Instructions
Special
Conditions
of Use
Hazardous Locations
Refer to Page 2 of this manual for all Special Conditions of Use for Hazardous Locations.
WARNING:
The AVT must be installed correctly and grounded as described in this Instruction Manual to provide proper indi-
cation of absence of voltage. Sensor leads must not be mechanically connected with each other for the device to
verify connection to the circuit. Correct function of the device must be verified after installation, see Commissioning
Checklist section, p. 15.
Sensor leads of the same label designation should be terminated on the same conductor (L1, L2, L3, GND). Each
conductor should have at least one sensor lead set, as shown on the schematic diagrams.
Excess length from Sensor Leads should be trimmed; lead wires should not be extended with a splice. When using
terminal or power distribution blocks, the total length of the sensor leads from the isolation module to the source
conductors shall not exceed 10 feet (3.0m).
Always comply with local installation codes and standards.
Always follow safety and lockout/tagout procedures when working on or near electrical systems and equipment.
NOTE: Before installation, verify that after power is removed from the circuit to be monitored. The potential measured
between each line and ground should be less than 2.7V, including voltages on the line from auxiliary systems.
ISOLATION MODULE NETWORK MODULE
DIN-RAIL MOUNTING
Snap the Isolation Module
onto the DIN rail.
OR SURFACE MOUNTING
Mount the isolation module
to any surface using four
#6 [M3.5] pan head
screws or another
compatible fastener.
Surface mounting with
screws is recommended
for high vibration
environments
ATTACHING NETWORK MODULE TO ISOLATION
MODULE (OPTIONAL)
If mounting
to isolation
module,
use screws
provided
with
network
module.
SENSOR LEAD TERMINATION
1. Route the sensor and ground leads.
The sensor leads should not be any longer than necessary and should be routed to avoid sharp edges, pinch points or mechan-
ical damage.
There is no maximum distance limitation between the two leads on each phase, however there should not be any circuit ele-
ments installed between them.
Sensor leads should not be extended with a splice. When using terminal or power distribution blocks, the total length of the
sensor leads from the isolation module to the source conductors shall not exceed 10 feet (3.0m).
2. Terminate the sensor and ground leads.
Use of ferrules or terminals is recommended.
Sensor leads for each phase and ground must not be mechanically terminated at the same point for the AVT to function proper-
ly.
Sensor leads of the same label designation should be terminated on the same conductor (L1, L2, L3, GND). Each conductor
should have at least one sensor lead set, as shown on the schematic diagrams.
Secure the sensor leads to the conductors and insulate the connections.
AUXILIARY DC POWER (OPTIONAL)
If using DC power, connect the 12 or 24 VDC power source, see DC Power Input (page 5). The DC Power Input is marked for polarity;
connect the positive output of the supply to the terminal marked (+) and the negative output of the supply to the terminal marked (-).