Panamax VT1512-IP handleiding

48 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 8 van 48
8
www.panamax.com
VT1512-IP Instruction Manual - English
Sample Response–
<status time=”1234567890”>
<voltage>119.14</voltage>
<voltpeak time=”0”>0.00</voltpeak>
<amperage>0.00</amperage>
<wattage>0.00</wattage>
<pwrva>0.15</pwrva>
<pwrfact>0.00</pwrfact>
<pwrcond>0</pwrcond>
<brkrfault>0</brkrfault>
<lastseqstate>1</lastseqstate>
<seq>0</seq>
<cycprog>0</cycprog>
<coprocop>1</coprocop>
<coproclink>1</coproclink>
<coprocimp>0</coprocimp>
<coproccrcerrs>0</coproccrcerrs>
<crcerrs>2</crcerrs>
<outlet id=”1”>1</outlet>
<outlet id=”2”>1</outlet>
<outlet id=”3”>1</outlet>
<outlet id=”4”>1</outlet>
<outlet id=”5”>1</outlet>
<outlet id=”6”>1</outlet>
<outlet id=”7”>1</outlet>
<outlet id=”8”>1</outlet>
<outlet id=”9”>1</outlet>
<outlet id=”10”>1</outlet>
<outlet id=”11”>1</outlet>
<outlet id=”12”>1</outlet>
<tlestate len=”0” chk=”4294967295” mtime=”4294967295” busy=”0” lock=”0” url=”” />
</status>
Details–
Element Description
voltage measured RMS line voltage, 1 Vac precision.
voltpeak measured peak voltage, 1 Vac precision. “time” attribute represents time of occurrence.
amperage measured total load current, 0.1 Ampere precision.
wattage measured total power consumption, 1 Watt precision.
pwrva measured volt-ampere consumption, 1 VA precision.
pwrfact measured load power factor, 0.01 precision.
pwrcond power condition: 0 = normal; 1 = fault recovery; 2 = under voltage; 3 = over voltage.
seq power sequence state: 0 = no sequence; 1 = sequencing ON; 2 = sequencing OFF.
cycprog group power cycle operation state: 0 = no cycle in progress; 1 = cycle in progress.
outlet state: 0 = outlet OFF; 1 = outlet ON. “id” attribute’s decimal value represents outlet number.
All other elements are for Nortek Security & Control use only.
Send Settings Query
The Send Settings query is used to retrieve the device conguration settings. Response settings elements are enclosed in the <settings> element.
Query–
<sendsettings/>
Sample Response–
<settings time=”1234567890”>
… (see Common Attributes section) …
</settings>
Details–
Element Description
settings device conguration settings. See Common Attributes section for details.

Bekijk gratis de handleiding van Panamax VT1512-IP, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkPanamax
ModelVT1512-IP
CategorieNiet gecategoriseerd
TaalNederlands
Grootte7259 MB