2.7.2 - Connections
Thechoiceandsizingofthehydrauliclinesmustbemadebyanexpertwhomustoperateaccordingto
therulesofgoodtechniqueandthelawsinforce.
Tomaketheconnections:
- position the hydraulic lines
- tightentheconnectionsusingthe“spannerandcounterspanner”method(g.12ref.B)
- checkforanyleaksofliquid
- coattheconnectionswithinsulatingmaterial(g.12ref.C).
The hydraulic lines and joints must be thermally insulated.
Avoid partially insulating the pipes.
Do not over-tighten to avoid damaging the insulation.
Usehempandgreenpastetosealthethreadedconnections;theuseofTeonisadvisedwhenthereis
anti-freeze in the hydraulic circuit.
2.8 - CONDENSATION DISCHARGE
Thecondensationdischargenetworkmustbesuitablysized(minimuminsidepipediameter16mm)and
thepipelinepositionedsothatitkeepsaconstantinclination,neverlessthan1%.Intheverticalinstal-
lation,thedischargepipeisconnecteddirectlytothedischargetray,positionedatthebottomoftheside
shoulderunderneaththehydraulicxtures.Inahorizontalinstallationthedischargetubeisconnectedto
the one already present on the machine.
ForinstallationoftheSLversionsinahorizontalposition,horizontalcondensationcollectionbasin
accessorykitsareavailableSL.
- Ifpossible,makethecondensationliquidowdirectlyinagutterora“rainwater”discharge.
- Whendischargingdirectlyintothemaindrains,itisadvisabletomakeasiphontopreventbadsmells
returningupthepipetowardstheroom.Thecurveofthesiphonmustbelowerthanthecondensation
collectionbowl.
- Ifthecondensationneedstobedischargedintoacontainer,itmustbeopentotheatmosphereandthe
tubemustnotbeimmergedinwatertoavoidproblemsofadhesivenessandcounter-pressurethatwould
interferewiththenormaloutow.
- Ifthereisaheightdi󰀨erencethatcouldinterferewiththeoutowofthecondensation,apumpmustbe
mounted(accessorykit):
- in a vertical installation mount the pump under the lateral drainage tray;
-inahorizontalinstallationthepumppositionmustbedecidedaccordingtothespecicrequirements.
Inanycase,consultthespecicinstructionsinthecondensationdischargepumpkit.
However, on completion of the installation it is advisable to check the correct outow of the
condensation liquid by slowly pouring about ½ l of water into the collection tray in about 5-10
minutes.
2.8.1 - Mounting the condensation discharge device in the vertical version
Connecttothecondensationcollectiontraydischargeunion(g.13ref.A)apipefortheoutowofthe
liquid(g.13ref.B)blockingitadequately.Checkthatthedrip-collectorextension(g.13ref.C)ispresent
and correctly installed.
2.8.2 - Mounting the condensation discharge device in the horizontal version
TomountthehorizontalbowlontheSLversionsrefertotheinstructionsintherelativeoptionalkit.
- Belowthesidecorrespondingtothecondensatedraintubeoutlet,cutthepre-cutarea(g.14ref.A).
- Retthesidepanel.