2-4-3. EMBEDDING THE INDOOR UNIT IN A WALL
1) Make a hole in the wall.
2) Using reinforcement material, adjust the depth.
3) Remove 6 screws that x the base to the unit. Remove the base from the unit.
4) Fix the indoor unit at 4 points with the included wood screws (9) and washers
(10). Tighten the screws securely.
4
575
740
70
4
3
3
3
3
3
3
705
2-4. INDOOR UNIT INSTALLATION
2-4-1. INSTALLING THE INDOOR UNIT ON THE FLOOR
1) Place the indoor unit on the at oor.
2) Fix the indoor unit at 4 points with the included wood screws (9) and washers
(10). Tighten the screws securely.
2-4-2. MOUNTING THE INDOOR UNIT ON THE WALL
1) Hook the top of the indoor unit on the indoor unit mounting bracket (7).
2) Fix the indoor unit at 4 points with the included wood screws (9) and washers
(10). Tighten the screws securely.
405
137
387
Indoor terminal block
Indoor/outdoor unit
connecting wire (A)
Outdoor terminal block
Earth wire
(green/yellow)
Make earth wire a little longer than others. (More than 45 mm)
For future servicing, give extra length to the connecting wires.
Do not fold the excess wire, or cram it into small space. Take caution not to
damage the wires.
Be sure to attach each screw to its correspondent terminal when securing
the cord and/or the wire to the terminal block.
2-5. CONNECTING WIRES FOR INDOOR UNIT
1) Remove VA clamp.
2) Pass indoor/outdoor unit connecting wire (A) from the back of the indoor unit
and process the end of the wire.
3) Loosen terminal screw, and connect rst the earth wire, then indoor/outdoor
unit connecting wire (A) to the terminal block. Be careful not to make mis-
wiring. Fix the wire to the terminal block securely so that no part of its core is
appeared, and no external force is conveyed to the connecting section of the
terminal block.
4) Firmly tighten the terminal screws to prevent them from loosening. After
tightening, pull the wires lightly to conrm that they do not move.
5) Secure indoor/outdoor unit connecting wire (A) and the earth wire with the VA
clamp. Never fail to hook the left claw of the VA clamp. Attach the VA clamp
securely.
Terminal block
Fixing screw
Indoor/outdoor unit
connecting wire (A)
VA clamp
Lead wire
35 mm
15 mm
Reinforcement
material
Unit
Base
When installing the unit, securely connect the refrigerant pipes before
starting the compressor.
WARNING