UNDERSTANDING AN AUTOPING CONFIGURATION
Page 55
Measuring Modem/Router Start-Up Time
When configuring AutoPing, it’s important to know the start-up time of the modem/router. The start-up
time is the amount of time between when the modem/router is powered-up until it starts routing traffic
to the Internet.
NOTE: If your Internet connection is down from your Internet Service Provider (ISP) or your AutoPing
settings don’t take your modem/router’s start-up time into account, the result is referred to as Cyclic
Rebooting, where your RackLink continuously turns the controlled outlet on and off.
To measure your modem/router start-up time:
1. Leave your modem/router unplugged/powered off.
2. Open a command prompt and Ping an address on the internet using the –t option (Ping
continuously) as follows:
ping –t www.google.com
You should see replies indicating “Request timed out”.
3. Start a stopwatch while plugging in the modem/router’s power cable.
Once you see “Reply from…” as a response, stop the stopwatch.
This is your start-up time for the modem/router.
NOTE: It may be beneficial to add a few seconds to the start-up time just to be safe. For our
example, we will assume the modem/router boots up in about 2 minutes.
Calculating Frequency, Failures, and Cycles
Before configuring AutoPing in your RackLink device, it’s important to understand the relationship
between Frequency, Failures, and Cycles. It is good practice to keep the default values for Frequency
and Failures (30 and 3, respectively) and adjust your outlet recovery cycle time (Cycle-Time) to equal
your measured recovery time from “Measuring Modem/Router Start-Up Time” on page 55, plus at
least 1 frequency.
In our example, we set Frequency to 30 seconds, Failures to 3, which results in your Internet
connection being down for 90 seconds in order to trigger an AutoPing recovery. Finally, we set an
outlet Cycle-Time of 150 seconds (a modem/router reboot of 120 seconds + a Frequency of 30
seconds).