Middle Atlantic RLNK-410R-IEC-NS handleiding

72 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 36 van 72
USING THE BROWSER-BASED INTERFACE
Page 36
NOTE: The Alert LED is red if any outlet has a failed AutoPing, or green if all outlets
indicate AutoPing replied.
In the Enabled field, select to turn AutoPing On or Off for the specific outlet.
In the IP Address field, enter the IP address of the Ping device.
In the Frequency field, enter how often (in seconds) your RackLink device initiates an
AutoPing. You can configure 30 - 999 seconds and the default is 30.
In the Retries field, enter the number of times your RackLink device will Ping the preset
address if no response is received. You can configure 2 - 200 retries and the default is 3.
For example, using the default settings with a Frequency of 30 seconds and three
Failures, the device being Pinged would need to be offline for 90 seconds before the
recovery action is executed.
In the Email Enabled field, select to turn email notifications On or Off for the specific
AutoPing from your outlet.
For more information, see “Configuring Email Settings” on page 44.
In the Recovery Action drop-down field, set a desired outlet action while the configured
Ping device does not reply. The actions cease whenever the Ping device does reply. The
actions include the following:
o Power-cycle Until Recovery
o Power-cycle Once
o Power Off Pending Recovery
o Power Off
o Power On Pending Recovery
o Power On
NOTE: Only one action per outlet can be performed at a time.
In the Cycle Time field, enter a cycle time delay value (in seconds) for the specific
AutoPing recovery action. You can configure the delay to be between 1 - 999 (inclusive)
seconds and the default is 3.
NOTE: The Cycle Time option only appears when the Power-cycle Until Recovery action
is selected.
7. Click Save.
TIP: To restore the default settings, see “Restoring Factory Defaults” on page 46.