Technical Manual Presence Detector SCN-x360xx.03
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 • Germany
Telephone: +49-2263-880 • knx@mdt.de • www.mdt.de
57
57
The individual parameters are described in more detail below:
Settings Switching behaviour/control behaviour
The general settings for the constant light control are made here. The parameter "Switch
constant light via…" can be used to set whether the control is switched via the detected
presence or via an external object, which can be connected to a push-button, for example.
The parameter "Controller switches the light off" defines whether the controller may
regulate the light to 0%, e.g. in the case of strong sunlight, and is thus switched off. If the
parameter is set to "not active", the outputs are not set to 0% but maintain a minimum value
that prevents the lamps from being switched off. This setting is useful in offices/workrooms,
as switching off the lighting is usually perceived as annoying. Furthermore, the dimming
range (minimum and maximum dimming value) for the CL can be limited.
The "Switch-on value Day/Night" parameter can be used to specify to the presence detector
the value with which the control is to be initialised. It is possible to define a fixed value, to
use the value adjusted during the Teach-in procedure or to have the switch-on value
calculated directly internally. The time until the control starts after switching on can also be
defined.
The parameter "Brightness value at switch-on" defines whether the control should always
work with the configured value or whether it should use the last setpoint value that was read
in, for example, via absolute/relative dimming or the scene function.
The control can also be configured here for different values for Day and Night. Day is active
as soon as the CL has been activated, Constant light control at Night can be additionally
activated via parameters. If not active, a fixed dimming value is set for switching on.
With the parameter "CL status sends value 1", it is possible to receive information about the
current status (standby, control active or lock active) via an object.
Settings: Dimming behaviour
The dimming value can be passed on both cyclically and at a specific percentage change.
The parameter "Behaviour of the CL on relative dimming" also defines whether the control
should be switched off by manual relative dimming or should continue to operate with the
new value.
Settings: Standby/Orientation light
The standby/orientation light defines a dimming after the constant light control has been
switched off. This means that if this parameter has been activated, the detector does not
switch the light off immediately, but to the set value for the specified duration.
Settings: Lock object
This displays a lock object which, when activated, locks the constant light control and causes
a certain forced position.
The following settings are available:
o OFF: The output is switched off (0%).
o ON: The output is switched on (100%):
o No change: The current absolute value is maintained.
o Settable value (only for locking): The set absolute value is called up.
o Restore previous state (only for unlocking): The absolute value that the constant light
control had before locking is recalled.