Technical Manual Presence Detector SCN-x360xx.03
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 • Germany
Telephone: +49-2263-880 • knx@mdt.de • www.mdt.de
25
25
4.2.4 Output objects
Light channel
HVAC channel
The following table shows the settings for the output object (here: Light channel/Switching):
Figure 14: Settings – Output objects
The following parameters are relevant for the output objects:
ETS-Text
Dynamic range
[Default value]
Comment
Object type for output –
Light
• Switching
• Dimming absolute
• Scene
Selection of the object type that is sent
when a motion is detected.
Output 2 (Additional
switch object)
• not active
• ON and OFF
Activation of an additional switching
object.
Only available for light channels!
Table 8: Settings – Output object
Output 2 (Additional switch object)
This object is only available for the light channels. In addition, a separate switching object can be
activated - regardless of the object type. This is always a 1-bit object.
If, for example, a dimming value is sent as output object 1, a 1-bit telegram can also be sent via
output 2 to control a status LED or similar.
Object type for output
The parameter defines the data point type of the output object.
These are explained below: