MDT SCN-P360L3.03 handleiding

65 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 21 van 65
Technical Manual Presence Detector SCN-x360xx.03
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 • Germany
Telephone: +49-2263-880 • knx@mdt.de • www.mdt.de
21
21
4.2.2 Basic settings HVAC
HVAC channel
The following picture shows the basic settings for an HVAC channel:
Figure 12: Basic settings HVAC channel
Die nachfolgende Tabelle zeigt die möglichen Einstellungen für diese Parameter:
ETS-Text
Dynamic range
[Default value]
Comment
Active sensors
----
1---
.
.
1234
Setting which sensors are active for this
channel.
With 3 sensors, the selection is
correspondingly "---" to 123".
With 2 sensors “--" to “12”.
Channel mode
fully automatic
half automatic (manual
switching)
Setting whether the device operates as a
fully automatic or semi-automatic device
Number of monitoring
time slots
1 30
[3]
Setting the number of observation time
windows
Length of monitoring
time slot
0 … 30000
[30]
Setting the length for each of the
observation time windows
Follow-up time Day
1 s 4 h
[3 min]
Setting the follow-up time for Day mode
Follow-up time Night
1 s 4 h
[30 s]
Setting the follow-up time for Night
mode
Table 5: Basic settings HVAC channel