Technical Manual Presence Detector SCN-P360D1.01
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-880 • Fax: +49-2263-4588 knx@mdt.de • www.mdt.de
23
23
4.6 Master/Slave
4.6.1 Light groups
In larger rooms often more than one presence detector is required. For detecting presence all over
the room, presence detectors must be allocated in the whole room. But also in this case a detected
presence shall cause always the same settings independent of the place of detection. In this case one
detector operates as Master and a arbitrary number of presence detectors work as Slave.
The settings for the Master/Slvae mode can be done in the submenu “light groups”.
The Slaves must be configured as follows:
Adjustment to fully automatic (every movement shall be sent)
Set follow-up time tot he same value as the Master
Activate cyclic sending for the output
o Parameter: Cyclical sending of object value ON
o Guidance value: 1min, at greater Follow-up time, e.g. 15min, the cyclical sending can
be set up to a greater value, e.g. 5min, for minimzing the bus load
Brightness value for “lower active brightness threshold” to maximum value
Brightness value for “upper disable brightness threshold” to not used
The Master can be parameterized as desired as fully automatic or semi automatic.
For the follow-up time a value of 10 min is recommended.
The connection of the objects must be done as follows:
all output objects of the Slaves (object 0) must be connected withe the object external
movement (object 3) of the Master.
Now the Master evaluates every degtected presence of itself and the detected presence of every
Slave and switches the light according to its settings, regardless which presence detector has
detected a movement.
4.6.2 HVC
The Master/Slave circuit can alos be used for HCV channels. In this case, the slave must be adjusted
in the same way as the slaves for the light groups. But the settings for the brightness values have not
to be applied. The settings for the monitoring time slots must be maded according to the individual
desires.
The connection of the communication objects must be done as follows:
All output objects of the slaves (object 0) must be connected to the object external
movement (object 10) of the Master.