Technical Manual Presence Detector SCN-P360D1.01
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-880 • Fax: +49-2263-4588 knx@mdt.de • www.mdt.de
22
22
4.4.1 Approach at Teach-In
For using the whole advantages oft he intelligent constant light control, the presence detector must
be adjusted once via the Teach-In process. Therefore a luxmeter is needed.
The approach is as follows:
1. Adjust the parameter “TeachIn brightness value” to the desired brightness value.
The best way doing the Teach-In process is to darken the room and switch the artificial lights
on. Now the brightness must be measured via a luxmeter and the measured value must be
set for the parameter “TeachIn brightness value”.
2. Adjust the Parameter “Use TeachIn value at application download” from “Use factory default
values” to “hold TeachIn values”.den gewünschten Wert.
3. Connect the object “18-Calibration start” with a new group address, if the calibration shall be
activated via the ETS (Group monitor) or with a push button.
4. Download the application.
5. Activate the Teach-In function by sending a logical 1 to the object 18.
6. Now the presence detector has adopted the adjusted value as new measurand and corrects
its measurement from now according to the TeachIn value.