Technical Manual Presence Detector SCN-P360D1.01
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-880 • Fax: +49-2263-4588 knx@mdt.de • www.mdt.de
18
18
4.3 Brightness
The following figure shows the available settings for the brightness detection:
Figure 7: Settings brightness
The following table shows the available settings for these parameters:
ETS-Text
Dynamic range
[Default value]
Comment
Send brightness on change of
not used
20 Lux 1800 Lux
[50 Lux]
Minimum rate of change for
sending the current brightness
Cyclical sending of light value
not used
5s 30min
Adjustment of a determined
time span for sending the
current brightness
Value for switching the
threshold switch
60Lux 1000 Lux
[30 Lux]
Adjustment of the threshold
for switching
Hysteresis of threshold switch
5 Lux 200 Lux
[30 Lux]
Distance between value for
switching ON and OFF
Object value on day for On
ON
OFF
Adjustment of the polarity
Object value on night for On
ON
OFF
Adjustment of the polarity
Object value for off
ON
OFF
Adjustment of the polarity