Technical Manual
CO2 / VOC Combi Sensor 55 [SCN-CO2MGS.02]
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Germany
Phone: +49-2263-880 • knx@mdt.de • www.mdt.de
59
59
A value above or below the reference value has no effect on the setpoint change. As soon as the
value is within the reference variable (i.e. between w
max
& w
min
), the setpoint is lowered or raised.
The following graphics are intended to illustrate the influence of the reference variable on the
setpoint:
(Xsoll=new setpoint; Xbasis=base setpoint)
Figure 29: Example Reference control/decrease
Figure 30: Example Reference control/increase
With the communication object of the reference value, the current temperature of the external
sensor can be read out. The communication object does not have to be linked with the
communication object of the setpoints to activate the command but is only used to request the
reference temperature.
The following table shows the corresponding object:
Number
Name/Object function
Length
Usage
97
Outside temperature Receive
measured value/Reference value
2 Byte
Receiving an external measured value as
a reference variable
Table 57: Communication object Reference via outdoor temperature