Technical Manual
CO2 / VOC Combi Sensor 55 [SCN-CO2MGS.02]
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 • Germany
Phone: +49-2263-880 • knx@mdt.de • www.mdt.de
19
19
4.2.3 Temperature measurement
The following settings are available:
Figure 7: Settings – Temperature measurement
The table shows the possible settings:
ETS-Text
Dynamic range
[Default value]
Comment
Send measured value
on change
• not active
• active
Setting whether the measured
value should be sent on change.
Send measured
value on change of
0.1 … 2 K
[0.1 K]
Setting at which change the
measured value should be sent.
Only visible if "Send measured
value on change" is activated.
Send measured value
cyclically
not active
1 min – 60 min
Setting whether and at what
interval the measured value is sent
cyclically.
Messages
• not active
• active
Activation of the message function.
Upper message
value
20 … 45 °C
[28 °C]
Setting range of the upper/lower
message value.
Only visible when parameter
"Messages" is activated.
Lower message
value
3 … 30 °C
[18 °C]
Calibration value for
internal sensor
-10 … 10 K
[0 K]
Adjustment for internal sensor.
Sensor
internal/external
• 100% internal
• 90 % internal/ 10 % external
• 80 % internal/ 20 % external
• …
• 10 % internal/ 90 % external
• 100 % external
• maximum value
Setting the weighting between
internal and external sensor.
Table 11: Settings – Temperature measurement